What Should I Know About Clearance Requirements When Installing My Generator?

Overview of residential standby generator clearance requirements to prevent fire and CO hazards, including NFPA 37 minimum distances (5 ft from openings, 18 in from the back to a stationary wall only for units marked with the SwRI logo, 5 ft above, and 3 ft at the front and ends), plus guidance on site selection to avoid airflow restrictions and water intrusion. Emphasizes that local codes take precedence, reduced clearances apply only to SwRI-labeled models, and installers should reference the generator’s installation manual; permitting, plumbing, and electrical work should be handled by qualified professionals.

Was this article helpful?
Upload Files


Need more help? Get in touch with our support team.


Contact Support